Egmec Industry Co., Ltd.
|
Payment Terms: | T/T,L/C,D/P,WU |
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Brief introduction:
DPS-003 Series of low differential pressure sensor is a high reliability, high stability, high - precision micro- differential pressure transmitter . Widely used in micro- differential detection of liquids, gases, water, oil, mildly corrosive liquids.
The product 1Cr18Ni9Ti stainless steel structure , imported pressure sensor, dedicated zoom in and V / I transmitter conversion circuit , specific anti- high voltage, high current , high magnetic field , the Promise of lead and other characteristics, through the intrinsically safe explosion-proof certification and CE certification.
According to the user programmed mode designed for the Zero and process the amount of change depending on the circumstances at the scene, two-wire system circulation output leads nonpolar; three-wire system the voltage output of the AC and DC.
Ordering:
Input signal | Connection type | Pressure portthreads | Addition |
A2=4~ 20mA B=0 ~5V D=1-5V E=0-10V | C=Cableline outlet GX=Aviation plug | Ø8Air nozzle | Va=8-30VDC M=Intrinsically safeexplosion-proof Exia IICT6 Ub=0.5%F.S |
Specification:
Item | Description | |
Pressure range | Within 0-1 kPa; 0-2.5 kPa;0-7kPa | |
Overload pressure | 3 Times the ratedpressure | |
Pipelinehydrostatic | 300kPa | |
Accuracy | ±0.5%F.S | |
Stability | Typical values: 0.5%F.S; Max. value: 1%F.S | |
Operationtemperature | -40℃ ~ 85℃ | |
Compensationtemperature | -10℃~70℃ | |
Compatible media | All corrosive mediacompatible with 1Cr18Ni9Ti | |
Quiescent operatingcurrent | Current consumption≤ 10m A meter of non- sampling | |
Output signal | 4-20Ma, 0-5V, 0-10V | |
Supply | 10-30VDC | |
Load resistance | >100K Ω, (U-10)/0.02(Ω) | |
Electricalconnection | Fixedline waterproof outlet , protection class to IP68 ; | |
Response time | ≤10ms | |
Pressure portthreads | Innerthread G1/4, hose connection , RG= Ø8 with Gas nozzle | |
Pressuretype | Differentialpressure | |
Lightningprotection | Airconduction withstand voltage 8000V, housing , cable conduction withstandVoltage 4000V | |
Electromagneticcompatibility | Electromagnetic radiation: EN50081-1/-2; Electromagnetic sensitivity: EN50082-2 |
Dimensions:
Connector type | ||||
Plug | 2-Wire | Cable | 3-Wire | Cable |
1 | Powersupply | Redwire | Powersupply | Redwire |
2 | Output | Blue/Green wire | Powersupply/ ground wire | Blackwire |
3 | Output | Blue/ Green wire | ||
GND | Shield | Yellowwire | Shield | Yellowwire |
Signaloutput | |
2 -Wire | 4- 20mA |
3 -Wire | 0-5V, 0.5-4.5V, 0-10V,0/4-10/20mA |